Kubota Generators - SQ Series - 4-Pole Three Phase - 26.3 kVA Output - SQ-26SW-3
|
MSRP: $15,900.00
Price: $13,900.00
You Save: $2,000.00 (13 %)
Model Number: SQ-26SW-3
|
- Type : Revolving field, brushless AC generator
- Frequency (Hz) : 60
- Standby Output kVA (kW) : 34.8 (27.8)
- Prime Output kVA (kW) : 33.1 (26.5)
- Voltage Single Phase : -
- Voltage - Three Phase : 480/240
- Armature Connection : Star with neutral
- Phase / Wire : 3-12
- Power Factor : 0.8
- No. of Poles : 4
- Insulation Class : H
- Voltage Regulation (%) : 2.5 (No load to full load)
- Type of Coupling : Direct coupled
AMPS
- Single Phase 120V (AMPS) : - -
- Single Phase 240V (AMPS) : - -
- Three Phase 208V (AMPS) : - 79.6
- Three Phase 480V (AMPS) : 39.8 -
- No. of Receptacles
- 5-15R (GFCI) : -
- 5-20RA (GFCI) : 1
- 6-15R : -
- L5-20R : -
- L5-30R : 1
- L6-30R : -
- L14-30R : 1
- CS-6369 : 2
Terminal
- Terminal : Available
Diesel Engine
- Type : Vertical, liquid-cooled, 4-cycle diesel engine
- Model : V3300
- No. of Cylinders : 4
- Bore x Stroke (in.) : (3.86 x 4.33)
- Displacement (cu. in.) : (202.5)
- Engine Speed (RPM) : 1800
- Continuous Rated Output (HP) : (40.1)
- Lubricant (API classification) : Above CF grade
- Oil Capacity (quarts) : (13.9)
- Coolant Capacity (quarts) : (10.0)
- Starting System : Electric 12 volt DC
Set
- Fuel : Diesel fuel No. 2 (ASTM D975)
- Fuel Consumption at Full Load (gallons/hour) : (2.38)
- Fuel Consumption at 3/4 Load (gallons/hour) : (1.84)
- Fuel Consumption at 1/2 Load (gallons/hour) : (1.40)
- Fuel Consumption at 1/4 Load (gallons/hour) : (1.01)
- Fuel Tank Capacity (gallons) : (21.5)
- Continuous Operation Hours at Full Load : 9.0
- Continuous Operation Hours at 3/4 Load : 11.7
- Continuous Operation Hours at 1/2 Load : 15.3
- Continuous Operation Hours at 1/4 Load : 21.4
- Battery (Ah/5h) : (12v x 92Ah)
- Dimensions (in.) Height x Width x Height : 81.9 x 36.6 x 41.8
- Sound Level (Full Load at 23 ft.) dB(A) : 65.0
- Emergency Stop System : In case of abnormal: Oil pressure, water temperature, fan belt broken, when the side cover and door open while running
Kubota Generator SQ Series
1. Super Quite
Over-Sized Muffler
Sound levels have been lowered by an over-sized muffler.
Second Muffler (for SQ-33SW only)
A special 2-stage muffler system is used in generators powered by the V3300 to reduce noise even further.
2. Easy Maintenance
Easy One-Side Maintenance
Engine oil and coolant drain extensions are provided to ease regularly scheduled maintenance. Oil gauge, oil filter, oil replenishment port, fuel filter, water reserve tank, battery and air cleaner are all located on one side for quick inspection and maintenance.
3. Safety
Safety Measures
All engines for SQ series generators are ECU-controlled. Automatic shutdown of the engine if abnormal condition (abnormal oil pressure or water temperature, excessive speed, broken fan belt) or if load center doors are opened during operation.
Locking Control Panel Door
Shields instrument panel from the elements and permits observation of all key functions without opening the door.
4. Operator Friendly
Transportability
One-point lifting eye makes it easy to transport all SQ series generators. Special forklift openings are located on the base of the machine.
Longer Continuous Operation
Large-capacity fuel tank (21.5gal; 81.4L) enables longer continuous operation on a single tank.
5. ATS
Access Terminals for ATS Make Wiring Easy
Access terminals for Automatic Transfer Switches (ATS) are located behind the left side of load center doors.
|